How to Calculate the Heating Requirements of a Warehouse

Warehouses often require carefully calculated heating solutions to ensure optimal working conditions, protect stored goods, and maintain energy efficiency. Unlike residential or small commercial spaces, warehouses present unique challenges such as large, open volumes, high ceilings, poor insulation, and varying external conditions. Calculating the heating requirements accurately is essential to achieving comfort, maintaining operational efficiency, establishing the right warehouse heaters and managing costs.

Understanding the Basic Principles

The process of calculating heating requirements involves determining the amount of energy (measured in kilowatts or kW) needed to maintain a desired internal temperature, given the external conditions. The main factors affecting this calculation include:

Building Heat Loss: Heat escapes through the building fabric (walls, roof, floor, windows, and doors) and ventilation.

Target Internal Temperature: The desired temperature inside the warehouse.

External Conditions: Average external temperature during the coldest period.

Air Changes Per Hour (ACH): Rate of air exchange due to ventilation, infiltration, or door openings.

The general heat loss formula used in warehouse heating calculations is Where:

  • Q = Total heat loss (kW)
  • U = U-value of the building fabric (W/m²K)
  • A = Surface area of the element (m²)
  • ΔT = Difference between internal and external temperatures (K)
  • Q_{ACH} = Heat loss due to air changes (kW)

Step-by-Step Calculation

Step 1: Define the Parameters

Internal Temperature (°C): Set the desired internal temperature, e.g., 16°C for warehouses storing goods or 18°C for human comfort.

External Temperature (°C): For UK climate conditions, the external temperature is typically assumed to be -1°C during winter.

Temperature Difference (ΔT): Calculate the difference between the internal and external temperatures.

Example: For an internal temperature of 16°C and an external temperature of -1°C:

Step 2: Calculate Heat Loss through the Building Fabric

Gather U-values: U-values indicate the thermal performance of each building element. These values can be obtained from building specifications, insulation data, or industry standards:

  • Walls (uninsulated): ~1.2 W/m²K
  • Roof (insulated): ~0.25 W/m²K
  • Windows: ~2.5 W/m²K
  • Doors: ~3.0 W/m²K

The lower the U-value, the better the insulation.

Calculate Surface Areas (A): Measure the surface area of each building element (walls, roof, doors, and windows) in square metres (m²).

Calculate Heat Loss: Use the formula for each element:

Example for walls: U = 1.2 W/m²K, A = 500 m², ΔT = 17°C

Repeat this calculation for each building element and sum the results to determine the total fabric heat loss.

Step 3: Calculate Heat Loss Due to Ventilation (Air Changes)

Warehouses are prone to high heat loss due to air infiltration and frequent door openings. Air changes per hour (ACH) measure the volume of air exchanged within the space. Typical values for warehouses range from 0.5 to 2 ACH, depending on door usage and building tightness.

The heat loss due to air changes is calculated using, Where:

  • Q_{ACH} = Heat loss from air changes (kW)
  • V = Volume of the warehouse (m³)
  • ACH = Air changes per hour
  • 33 = Air-specific heat capacity constant (kJ/m³K)
  • ΔT = Temperature difference (K)

Example Calculation:

  • Warehouse dimensions: 50m x 30m x 10m (Volume = 15,000 m³)
  • ACH = 1.5
  • ΔT = 17°C

Step 4: Total Heating Requirement

The total heating requirement is the sum of the heat losses due to the building fabric and air changes:

Example Summary:

  • Heat loss through building fabric: 25 kW
  • Heat loss due to air changes: 126 kW
  • Total heating requirement: 25 + 126 = 151 kW

Selecting the Heating System

Once the total heating requirement has been calculated, it is essential to select an appropriate heating system. For warehouses, the most common options include:

  • Warm Air Heaters: Ideal for large spaces, distributing heated air quickly and evenly.
  • Radiant Heaters: Suitable for zones with high ceilings and where spot heating is required.
  • Destratification Fans: Help circulate warm air trapped at ceiling levels to reduce heat loss.

Considerations for System Selection:

  • Energy Source: Gas, electric, or renewable energy solutions.
  • Efficiency: Systems with high energy efficiency ratings to minimise running costs.
  • Controls: Thermostats, timers, and zoning controls for better temperature management.

Optimising Energy Efficiency

Heating warehouses can be costly, but energy efficiency measures can significantly reduce energy consumption:

Improved Insulation: Insulating walls, roofs, and floors reduces heat loss.

Sealing Gaps: Minimising air infiltration through doors, windows, and joints.

High-Speed Doors: Reducing the time doors remain open prevents heat escape.

Smart Controls: Using programmable thermostats to optimise heating schedules.

Destratification Fans: Ensuring even temperature distribution.

Final Thoughts

Calculating the heating requirements of a warehouse involves understanding heat losses through building fabric and ventilation. By following the step-by-step approach outlined above, you can determine an accurate heating load, ensuring a well-sized and energy-efficient system. Proper insulation, effective heating solutions, and optimised controls are key to maintaining operational efficiency and managing energy costs in warehouse environments.

If in doubt, contact us here at Newsome, and we can help you establish the permanent or temporary heater hire needs of your warehouse facility, factory, or office.